Overload protection                                                                                                                                             
Ib £ In £ Iz
If £ 1,45 Iz
were Ib = Operating current of the circuit
In = rated current of the protective device
Iz = the current-carrying capacity of the cable
If = operating current of the protective device
current-carrying capacity of cables  "Iz"  according to the tables of  IEC 364-5-523


Protection against Short Circuits                                                                                                                                              
IccMax £ P.d.i.
I²t =< K²S²
dove IccMax = maximum short-circuit current
P.d.i. = power interruption protection equipment
I²t = Joule integral of the short-circuit current
K = coefficient  that is used
115 for PVC insulated cables
135 for rubber insulated cables natural and butyl
143 for ethylene propylene rubber insulated cables and cross-linked polyethylene
S = section of the cable
Let-through  energy                                                                                                                                               
I²t £ K²S²
dove I²t = value read on the curve let-through energy I²t protection in
                                           correspondence of the short circuit currents
K²S² = let-through energy of the cable
dove K = coefficient of cable type (115,135,143)
S = cable section
f
 
 
 
ELECTRO-AREA
POWERS LINE BT


tag:

overload protection  short circuit protection let-through energy

Copyright 2014 © ELECTRO-AREA , Alessandro Di Santo,  e-mail: staff.electroarea@yahoo.it
cookie policy
Overload protection

Protections against short circuit

Let-through energy

Voltage drop

Calculation of the current-carrying capacity and voltage drop of a three phase power line

Calculation for verifying the protection of cables against overload and short-circuit

Formulas e tables used in the calculations online
[HOME][POWERS LINE BT][SHORT CIRCUIT CURRENT][ELECTRICAL GROUNDING SYSTEM ]
Italian version